SciencePhysics

Heat Transfer
calculator.

Heat flow by conduction, convection or radiation, and the energy to warm a mass.

How it's worked out

Conduction is heat passing through a solid layer, such as a wall. Fourier's law says the flow grows with the conductivity k, the area A and the temperature difference, and it falls as the layer gets thicker.

Q\displaystyle Q=kAΔTd\displaystyle {}= \frac{k A \Delta T}{d}

The thickness over the conductivity is the layer's thermal resistance, and a good insulator has a large one. Metric tables call it RSI. US tables quote the same idea in other units, and NIST gives the factor: one US unit is 0.1761102 m²·K/W.

R\displaystyle R=dk\displaystyle {}= \frac{d}{k}

Convection is heat carried off by a moving fluid. Newton's law of cooling wraps the fluid, its speed and the surface into one coefficient h, which is still known mainly through experiments.

Q\displaystyle Q=hAΔT\displaystyle {}= h A \Delta T

Radiation needs no material between the surfaces. The net flow depends on the fourth power of each temperature in kelvin, times the emissivity ε (a number from 0 to 1) and the Stefan–Boltzmann constant, σ, which NIST lists as exact at 5.670374419 × 10⁻⁸ W/(m²·K⁴).

Q\displaystyle Q=εσA(T14−T24)\displaystyle {}= \varepsilon \sigma A \left(T_1^4 - T_2^4\right)

Heating is different. It gives an amount of energy in joules, not a rate in watts, using the mass and the specific heat. That law holds only while the material does not melt or boil.

Q\displaystyle Q=mcΔT\displaystyle {}= m c \Delta T

Worked examples

Priya checks an insulated wall

Priya has 10 m² of 100 mm glass fiber, with the warm side 20 °C above the cold side. At k = 0.04 W/(m·K), the layer passes 80 W. Over a full day that is 1.92 kWh.

Its RSI is 2.5 m²·K/W, or about R-14.2 in US units. Doubling the thickness to 200 mm halves the flow to 40 W, so the second 100 mm saves less than the first one did.

Open this example in the tool

Marco asks why a window is not losing thousands of watts

Marco enters a 5 mm pane with 20 °C across it and gets 5,600 W for each square meter. That figure assumes the glass faces sit at the room and outdoor temperatures, and they do not.

Thin air layers cling to both faces. MIT's building notes put them near 1 and 0.33 in US resistance units, which is 0.176 and 0.0581 m²·K/W. The glass adds only 0.00357. Resistances in a row add, so the flow falls to about 84.1 W per square meter, and the glass itself hardly matters.

Open this example in the tool

Ana sizes the loss from a hot pipe

Ana has a pipe at 100 °C in a 20 °C room, with an emissivity of 0.9. Each square meter radiates a net 613 W.

The same surface also loses heat to the air. At h = 10 W/(m²·K), the 80 °C gap adds 800 W per square meter. Work out each path on its own and add them, because they run side by side.

Open this example in the tool

Reading your result

Watts are a rate and joules are an amount. A flow of 1 W for one second moves 1 J, so a steady flow becomes a bill only once you pick a time. A negative result in the first two modes means the heat runs the other way.

R-value belongs to the material and its thickness, and it does not depend on the area. Layers in a row add. OpenStax quotes R-11 for a 3.5 inch fiberglass batt and R-19 for a 6.5 inch one, so you can check your figure against those. Studs conduct better than the insulation between them, so a framed wall does worse than its insulation alone.

The conductivities offered in the material list are typical figures near room temperature. Handbooks differ with grade and temperature. OpenStax lists copper at 390 W/(m·K) near 0 °C and glass at 0.84, where the list uses 401 and 1.4. For real work, use the figure from your product's data sheet.

The coefficient h is only known roughly. The table in MIT's notes puts gases in natural convection near 2.8 to 280 W/(m²·K), and liquids in forced convection near 170 to 5,700, after converting from US units. Those are sizes to start from, not values to quote.

Common mistakes

  • Celsius in the radiation law. The fourth powers need kelvin. Typing 100 and 20 as kelvin gives 5.1 W per square meter in place of 613 W.
  • Mixing up a difference and a temperature. A difference of 1 K equals a difference of 1 °C, so conduction and convection accept either. A difference of 1 °F is only five ninths of that.
  • Comparing RSI with a US R-value. They differ by a factor of about 5.68, so RSI 2 is about R-11.4, slightly better than R-11 though its digits look far smaller.
  • Using the layer alone for a window or a thin sheet. Thin layers barely resist heat, so the air films set the result.
  • Using the heating law through a change of state. Melting water takes 334 kJ/kg and boiling it takes 2,256 kJ/kg, per OpenStax, on top of any warming.

Questions people ask

There is no one number, since h depends on the shape, the size and the temperature gap. Published ranges for still air run from single digits to a few tens of W/(m²·K), and very hot surfaces lose more by radiation too. Start with 10, then run 5 and 25 to see how much your answer moves.

Sources